FEATURES
- Digital circuit with high speed microprocessor MCU control.
- Have parameter setting through programmable logic device.
- Self-test and self-detective analysis.
- Excellent load characteristics: It is completely satisfy to load from 0 to 100% load variation without switch to bypass, which to protect the output more stable and reliable.
- Many kinds of system protection and alarming function: With the input/output over voltage and under voltage protection, input surge protection, battery overcharge and over discharge protection, output overloading, short circuit protection, high temperature protection.
- High-powered dynamic characteristics: Adopt immediate control mode and effective value kind of feedback control, realized the high dynamic adjustment, reduce the output voltage degree of distortion.
- Personalized Settings: It can be setting the UPS working status on the LCD according to the user demand side management. User can optional switch to UPS working mode and EPS working mode.
APPLICATIONS
- Major Power Back up source in corporate offices as well as call centres.
- Banks &ATMs.
- Defence & Para Military operations complex.
- Life saving medical equipments and diagnostic labs.
- Photography and colour labs.Emergency Devices (Lights/Alarms)
- Fire Devices.
- Telecommunication Devices.
- Industrial Applications.
- Vital real time & process control equipment in industries.
- Aviation and Broadcasting
SPECIFICATION
CAPACITY | ||||||||
---|---|---|---|---|---|---|---|---|
KVA | 3 KVA | 5 KVA | 7.5 KVA | 10 KVA | 7.5 KVA | 10 KVA | 15 KVA | 20 KVA |
WATT | 2.4 KW | 4 KW | 5.8 KW | 8 KW | 5.8 KW | 8 KW | 12 KW | 16 KW |
TYPE | Low Freuqency Transformer Based True On Line_Double Conversion | |||||||
INPUT | ||||||||
Phase | single phase ( P + N ) | three phase ( 3 P + N ) | ||||||
Input Voltage Range | 230VAC ± 25 % | 400 VAC ± 20 % | ||||||
Input Power Factor | 0.85 | |||||||
Input Frequency Range | 50Hz ± 10 % | |||||||
Output Ripple | < 5 % | |||||||
Soft Start | 0-100 % 5 sec | |||||||
OUTPUT | ||||||||
Nominal Voltage | 220VAC (230VAC or 240VAC), 1P + N | |||||||
Output Voltage Regulation | ±1 % ( linear load), ± 3% ( non linear load) | |||||||
Output Frequency Range | 50Hz ± 0.5% | |||||||
Crest Factor | > 3:1 | |||||||
Distortion (THD) | linear load < 3%, non linear load<5% | |||||||
Dynamic Characteristics | instant voltage < ± 2% ( from 0 to100% ),instant recover time < 5 ms | |||||||
Overload Capacity | 110% for 60 minutes | 125% for 10 minutes | 150% for 60 seconds | |||||
Inverter Efficiency | >92% ( full load ) | |||||||
BATTERY | ||||||||
Nominal DC Voltage | 96 Vdc | |||||||
Temp. Compensated Voltage | -3mV/°C/cell | |||||||
Charging Current | 2-10 amp setable | |||||||
Low Voltage Alarm | alarm contineous when power supply by battery and without main power. | |||||||
Low Voltage Trip | battery low-voltage protection, alarm stop. | |||||||
BY PASS | ||||||||
Phase | single phase ( P+N ) | |||||||
Manual | maintenance by pass switch provided | |||||||
Static | no break | |||||||
PROTECTION | ||||||||
Input Protection | input voltage, frequency under, over limit protection | |||||||
Output Protection | over current, short circuit, over voltage, low voltage | |||||||
Battery Protection | over charge, over - discharge protection | |||||||
Temperature Protection | inverter over temperature protection | |||||||
GENERAL PARAMETERS | ||||||||
Working Environment | temp: -10-40°C, relative humidity: 30%-90% | |||||||
Cooling Method | compulsive ventilation | |||||||
Communitation Interface | RS232/ RS485, optional dry contact, SNMP card ( for remote control via internet ) | |||||||
Parallel Operation | hot stand by or parallel redundant | |||||||
Protection Level | IP20 | |||||||
Safety Performance | V in-n, V out-n 2000Vac, creepage<10mA , insulating resistance >2 MO (500VDC) | |||||||
Noise (dB) | 45 - 50 | 50 - 60 | 55 - 65 | |||||
Dimension WXHXD (MM) | 345 X 660 X 610 | 390 X 680 X 680 | 410 X 780 X 740 | |||||
Weight (Kg) | 53 | 63 | 96 | 104 | 98 | 108 | 135 | 192 |

UPS Uninterruptible Power Supply
FEATURES
- Advanced DSP Technologyfor stable operation
- Intelligent Battery Management
- Excellent load characteristics
- Many kinds of system protection and alarming function
- Personalized Settings For Parameters
- Digital circuit with high speed microprocessor MCU control
- Intelligent battery management
- Intelligent detection system
- All parameter shown in LCD screen
- LED status indicators
APPLICATIONS
- LAN Servers
- Data Centres Inter
- Internet Centres (ISP/ASP/POP)
- Industrial PLCs
- Emergency Devices (Lights/Alarms)
- Electro-Medical Devices.Telecommunication
- Devices.Industrial Applications
MODELS | 10 | 15 | 20 | 30 | 40 | 50 | 60 | 80 | 100 | 120 |
KVA | KVA | KVA | KVA | KVA | KVA | KVA | KVA | KVA | KVA | |
INPUT | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Nominal voltage | 380 / 400 / 415 Vac three-phase + N | |||||||||
Voltage range | ±25 % | |||||||||
Nominal frequency | 50 Hz | |||||||||
Frequency tolerance | 50 ± 5 % Hz | |||||||||
Bypass voltage range | ± 20 % ( Settable ) | |||||||||
Eco voltage range | ± 10 % ( Settable ) | |||||||||
OUTPUT | ||||||||||
Active power (kW) | 8 | 12 | 16 | 24 | 32 | 40 | 48 | 64 | 80 | 96 |
Power factor | 0.8 | |||||||||
Number of phases | three-phase + N | |||||||||
Nominal voltage (V) | 380 / 400 V 415 ± 1 % @ full load | |||||||||
Crest factor | 3 : 1 I peak /I rms | |||||||||
Frequency | 50 Hz ± 0. 1 % on battery mode | |||||||||
Crest factor | 3:01 | |||||||||
THDV | 2 % with linear load / 5 % with non-linear load | |||||||||
BATTERIES | ||||||||||
Type | VRLA AGM/GEL/NiCd/Li-ion/Supercaps | |||||||||
Charging Amp. | 5 Amp default ( settable ) | |||||||||
Charging | Three stage charging, auto switch floating / boost mode | |||||||||
OTHER PARAMETERS | ||||||||||
Protections | Over load, over volatge, under voltage, low battery, over temperature, short circuit | |||||||||
Operating temperature | 0 °C - 40 °C | |||||||||
Relative humidity | 90% non-condensing | |||||||||
Noise level | < 65 dB | |||||||||
IP rating | IP20 | |||||||||
Communications | RS 2321 RS 4851 Dry contacts / SNMP ( Optioal ) | |||||||||
Moving the UPS | castors (10 - 50 kVA) I Pallet (60 - 120 kVA) | |||||||||
Weight ( Kg) | 125 | 145 | 180 | 215 | 280 | 320 | 530 | 580 | 750 | 800 |
Dimensions (WxDxH)(mm) | 390 x 690 x 855 | 410x 780x1000 | 460x 780x1260 | 775 x 900 x1500 | 1150x 1025x1600 |